Rev. B1, 5/13 MNU Series Ultrasonic Sensors
33
Automa! on Products Group, Inc.
APG...Providing tailored solu• ons for measurement applica• ons
•Web Alarming (40430 to 40435)
When the MNU is interfaced with an LOE or RST-5002 web-enabled master
device, it can be confi gured to generate website alarms via levelandfl ow.com
(refer to the LOE or RST-5002 user manual for more informa# on about website
alarms and using levelandfl ow.com).
Trip Alarm 1 (40430) or Alarm 2 (40433) Distance
Sets the level (in mm), beginning the bo$ om of the stem, to the fi rst (lowest)
actua# on point (refer to next page for more informa# on).
Trip Alarm 1 Window (40431 or 40434)
Sets the level (in mm), beginning from the Trip Distance loca# on, to the second-
ary actua# on point (refer to next page for more informa# on).
Trip Alarm 1 Type (40432 or 40435)
Determines the opera# onal logic performed by the Trip Alarm (refer to chart on
next page for more informa# on).
Confi guring Trip Alarm Types for Website Alarming:
(refer to Trip Types chart on next page)
Placing a “1” in front of any of the Trip Types designates an ac# ve trip point as
an alarm condi# on. For example; Trip Type 3 would be designated as 13, and
would ini# ate a website alarm whenever the trip is ac# ve (on).
Placing a “2” in front of any of the Trip Types designates an inac# ve trip point as
an alarm condi# on. For Example; Trip Type 3 would be designated as 23, and
would ini# ate a website alarm whenever the trip is inac# ve (off ).